- Part Number: 416146
- EAN: 3414970400765
- Rating: 50A (AC-3) switching of 3Phs motors up to 22kW(415V).
- Resistive Loads: Up to 70A(AC – 1).
- Screw terminal capacity: Power – 2 x 6mm2 to 25mm2 / Coil – 0.75mm2 to 2.5mm2/ Aux.circuit – 0.75mm2 to 2.5mm2.
- 2NO+ 2NC auxiliary contacts.
- According to IEC 60947 – 4 – 1 standards & can be equipped with all Legrand CTX3 auxiliaries and accessories.
- Endurance: Up to 12million mechanical operations and 2million electrical operations.
- of operation cycles: (AC-3)/ Hr: 1800
Reccomendation/Restriction
- This product is specifically designed for tertiary & Industrial installation.
- To use for the switching of inductive and non inductive loads.
TECHNICAL CHARACTERISTICS
Rated control supply voltage AC 50 HZ | 195.5-253 V |
Rated control supply voltage AC 60 HZ | 195.5-253 V |
Voltage type for actuating | AC |
No.of normally closed contact as main contact | 0 |
No.of normally opened contact as main contact | 3 |
Type of electrical connection of main circuit | Cable clamp |
Rated operation current le at AC-1, 400V | 70A |
Rated operation current le at AC-3, 400V | 50A |
Rated operation power at AC-3, 400V | 22kW |
Rated operation current le at AC-4, 400V | 32A |
Rated operation power at AC-4, 400V | 15kW |
No.of auxiliary contact as normally opened contact | 2 |
No.of auxiliary contact as normally closed contact | 2 |
Suitable for Distribution board | Yes |
Usage
It can be fitted with 2NO+2NC auxiliary contact, factory assembled. Designed to allow an easy replacement of the coil.
Advantage
- Coil supply possible either on the top or the bottom side.
- Front cover can be removed for the visual inspection of arc chambers and contacts.